SymbolsTransformerRelayPower-SystemBasic-electricalACSR-ConductorCircuit-BreakerInterview-questions-of-Basic-ElectricityInterview-questions-of-transformerInsulatorCurrent-TransformerMCQMCQ-powersystemThermal-power-stationInterview-questions-of-Power-SystemPower-ElectronicsInterview-questions-of-Underground-CableInterview-questions-of-IlluminationIlluminationMCQ-of-ElectronicsMCQ-of-Basic-ElectricalMCQ-of-Transformers MCQ-of-D.C-motor MCQ-of-D.C-generatorsMCQ-Control-SystemMCQ-Measurementsmcq-of-Generation-power-systemMCQ-of-Induction-MotorMCQ-of-Transmission-DistributionMCQ-of-Electrical-MachinesMCQ-of-Alternator-and-Synchronous-Motors

Multiple Choice Question (MCQ) of Power Systems page-11


≪ Previous Next ≫

121. Which of the following statement is true if restricted earth fault protection is provided to star winding of the generator transformer

a) One CT in each phase and fourth in the neutral are provided and their secondaries are connected in parallel
b) One CT is provided in the neutral
c) Two CT are provided, one in R-phase and other in Y-phase with a CT in neutral
d) In fact CTs are not required at all the fault current is not very high

Ans: (a)

122. Series capacitors are used to

a) Improve line voltage
b) Compensate for line inductive reactance
c) Compensate for line capacitive reactance
d) None of the above

Ans: (b)

123. Air blast circuit breakers for 400 kV power system are design to operate in

a) 5 sec
b) 0.5 sec
c) 0.1 sec
d) 50 millisecond
e) 100 micro-second

Ans: (d)

124. Carrier transfer-trip schemes do not operate faster than carrier blocking schemes

a) True
b) False

Ans: (b)

125. The auxiliary power supply system in any kind of power station is arranged such that the power supplies are

a) Redundant only
b) Redundant and independent only
c) Reliable
d) Independent
e) None of the above

Ans: (b)

126. High water level of a boiler drum can damage

a) Boiler tubes only
b) Turbine and steam line
c) Turbine only
d) None of the above

Ans: (c)

127. Which of the following statement is true ?

a) The zero sequence reactance of a transformer is approximately equal to negative sequence reactance.
b) The zero sequence reactance of transformer is approximately equal to positive sequence reactance.
c) The zero sequence reactance depends on the connection and winding of the transformer.
d) The zero sequence reactance is large than negative sequence reactance but less than positive sequence reactance in the transformer.

Ans: (c)

128. The capacity voltage transformer is used

a) Upto 11 kV
b) Upto 33 kV
c) Above 220 kV
d) Above 132 kV
e) Above 110 kV

Ans: (d)

129. The MHO relay inherently a

a) Directional unit
b) None-directional unit
c) None of the above

Ans: (a)

130. The operation time of instantaneous relay is usually

a) Of an order of a few second
b) Without any time delay
c) One second
d) 0.01 second

Ans: (d)


≪ Previous Next ≫


Related topics :


Recent Post

Multiple Choice Question (MCQ) of Electric Power page-10:
91. An impulse turbine
A) operates by initial complete conversion to kinetic energy
B) is most suited for low head installations
C) making use of a draft tube
D) always operates submerged.

Read more...

Multiple Choice Question (MCQ) of Electric Power page-9:
81. Spouting velocity is A) Velocity of jet under specified conditions
B) Actual velocity of jet
C) 50 % of ideal velocity of jet
D) Ideal velocity of jet.

Read more...

Multiple Choice Question (MCQ) of Electric Power page-8:
71. In closed cooling system A) water does not flow
B) hot water is recirculated after cooling
C) air and water cooling is simultaneously used
D) constant supply of fresh water for cooling is required.

Read more...